WaytoICT › 香农学术库 › ECOC 2026 › 论文

基于在运光纤复合架空地线的110 kV架空线路检修作业分布式传感

Distributed Sensing on a 110-kV Overhead-Line Maintenance Operation on an Operational Optical Ground Wire
光传感分布式声波传感(DAS)光传感实验
ECOC 2026Adtran
在110kV OPGW上实现DAS+DTSS双模态分布式传感,验证吊装事件与残余应变。

基本信息

作者
Konstantinos Alexoudis(1,2), Torm Järvelill(3), Hendrik Johann Kerm(3), Kaida Kaeval(3), Florian Azendorf(1), Vincent Sleiffer(1), Jasper Müller(1), Chigo Okonkwo(2), Tom Bradley(2)
机构
Adtran
国家
Germany
会议
ECOC 2026(European Conference on Optical Communication)

摘要

我们在一条运行中的110-kV OPGW上、于吊车检修作业期间演示了双模态分布式传感。DAS可分辨米级起吊事件,并将冲击性事件与手机音频相匹配;DTSS则量化重新夹紧后的残余应变,最高约∼398 µϵ,从而为输电网的检修验证和资产监测提供支持。

Abstract

We demonstrate dual-modal distributed sensing on an operational 110-kV OPGW during crane maintenance. DAS resolves meter-scale lifting events and matches impulsive events to phone audio, while DTSS quantifies post-reclamping residual strain up to ∼398 µϵ, enabling maintenance verification and asset monitoring in transmission grids.

关键技术指标

指标数值说明
传感架构DAS + DTSS 双模态分布式传感同一根 OPGW 光纤上同时进行振动与应变测量
应用场景110-kV 运行中 OPGW吊车检修作业期间在线监测
空间分辨率米级DAS 可分辨起吊事件
残余应变约 398 µε重新夹紧后,由 DTSS 量化,取最高值
事件识别能力冲击性事件与手机音频匹配由 DAS 声学信号比对验证
功能定位检修验证 + 资产监测支撑输电网维护作业验收